Detectors

Replacing NSC detectors (Hochiki and Apollo): types, successors and bases

Which NSC, Hochiki and Apollo detectors manufactured from 2000 onwards must be replaced, what is still available, which detector replaces older types and when a new base is needed – with the manufacturers’ order numbers.

← All manufacturers at a glance

Detector age

How old is the detector – how long has it been in operation?

  • Hochiki / Apollo (NSC, Labor Strauss, MEP, Hertek): The detector label shows a date code or the serial number, from which the year of manufacture can be derived. The commissioning date can be found in the system’s logbook and records.
  • Logbook and reports (decisive): The operating time counts from the commissioning of the detector. The date is recorded in the logbook, in the commissioning or acceptance report or in the last replacement report. This gives the years and months in operation.
  • Type plate on the detector: The label (usually on the underside or side of the detector, visible after twisting it out of the base) shows the type, serial number and date of manufacture or a date code (e.g. year/calendar week). If no commissioning date is documented, we take the cautious approach of calculating from the date of manufacture.
  • Reading out via the panel: With many addressable loop detectors, detector data such as serial number, date of manufacture, degree of contamination and – depending on the system and software version – operating hours can be retrieved via the panel’s operating unit or programming software. We do this during the survey using your programming file.

This determines the replacement interval under DIN 14675: as a rule 5 years, or 8 years for detectors with contamination compensation and testing in accordance with the manufacturer’s specifications – details under Deadlines & standards. Send us a photo of the type plate and we will determine the age for you.

NSC Sicherheitstechnik

Which NSC detector do you have installed?

The fire alarm control panels Solution F1/F2 from NSC Sicherheitstechnik work with detectors from Hochiki or Apollo – depending on the system. Which family is installed is shown on the detector: ALN-, ACC-, ACD-, ATJ-…-EN = Hochiki ESP (addressable loop), SOC-, DCD-, DFJ-…E3 = Hochiki CDX (conventional); XP95, Discovery, Soteria = Apollo addressable loop, Orbis and Series 65 = Apollo conventional. NSC lists the detectors under its own item numbers (Bxxxxx-xx); for Apollo we also give the manufacturer’s code. Apollo detectors and bases are not only found in NSC systems: for Germany, Austria and Switzerland, Apollo also lists Labor Strauss (Labor Strauss Sicherungsanlagenbau, Labor Strauss Sicherheitssysteme and Labor Strauss Sicherheitssysteme Nord), MEP-Gefahrenmeldetechnik (Labor Strauss Group) and Hertek as system partners. The information on Apollo detectors and bases applies equally to these systems; the Apollo manufacturer’s code is decisive.

Images: NSC Sicherheitstechnik / Hochiki / Apollo. Examples shown; housing colour and labelling may vary by type.

No longer available

NSC with Hochiki detectors: replace older types, base remains

Older Hochiki detectors of the ESP loop series and the CDX conventional series are being replaced by the current generation. The successors fit the existing bases YBN-R/3 (ESP) and YBN-R/6 (CDX) respectively – the base remains.

Hochiki ESP (addressable loop) and CDX (conventional)

ImageOld detectorOld typeAvailable?Alternative detector (NSC item no.)New base?
Optical addressable loop detector Hochiki ESPOptical addressable loop detector ESPALG-ENno – discontinuedALN-EN (NSC B02002-00)no – YBN-R/3 remains
Optical addressable loop detector Hochiki ESPOptical addressable loop detector ESP, older versionALG-Eno – discontinuedALN-EN (NSC B02002-00)²no – YBN-R/3 remains
Multi-sensor detector Hochiki ESPMulti-sensor addressable loop detector ESPACA-Eno – discontinuedACC-EN (NSC B02011-00)²no – YBN-R/3 remains
Heat detector Hochiki ESPAddressable loop heat detector ESPATG-EAno – discontinuedATJ-EN (NSC B02021-00)²no – YBN-R/3 remains
Multi-sensor detector Hochiki ESPIonisation smoke detector ESPAIE-Eno – discontinuedACC-EN (NSC B02011-00) or ACD-EN (NSC B02015-00)¹no – YBN-R/3 remains
Smoke detector Hochiki CDXOptical smoke detector CDX (conventional)SLR-E3Nno – discontinuedSOC-E3N (NSC B03003-00)²no – YBN-R/6 remains

¹ Ionisation detectors are no longer manufactured. Which detector replaces them depends on the fire detection and alarm concept – we agree this with you. ² Functionally equivalent successor; we check using your detector list and programming file whether the type runs on your control panel without reprogramming.

Current series

Hochiki ESP and CDX: same detector, same base

NSC currently stocks these Hochiki detectors. When replaced on schedule, the detector is exchanged for the same type and the existing base remains. Detectors with SCI have integrated isolators and belong to the ESP Top Loop technology.

ImageDetectorsItem no. (NSC)Available?Replace withNew base?
Optical addressable loop detector Hochiki ESPOptical addressable loop detector ALN-ENNSC B02002-00yessame typeno – YBN-R/3 remains
Optical addressable loop detector Hochiki ESPOptical addressable loop detector ALN-EN SCI (with isolators)NSC B02003-00yessame typeno
Multi-sensor detector Hochiki ESPMulti-sensor addressable loop detector ACC-ENNSC B02011-00yessame typeno
Multi-sensor detector Hochiki ESPMulti-sensor addressable loop detector ACC-EN SCI (with isolators)NSC B02012-00yessame typeno
Multi-criteria detector Hochiki ESPMulti-criteria addressable loop detector ACD-EN (O/T/CO)NSC B02015-00yessame typeno
Heat detector Hochiki ESPMulti-heat addressable loop detector ATJ-ENNSC B02021-00yessame typeno
Heat detector Hochiki ESPMulti-heat addressable loop detector ATJ-EN SCI (with isolators)NSC B02023-00yessame typeno
Heat detector Hochiki ESPMulti-heat addressable loop detector ACB-EW, IP67NSC B02022-00yessame typeno
Smoke detector Hochiki CDXOptical smoke detector SOC-E3N (conventional)NSC B03003-00yessame typeno – YBN-R/6 remains
Heat detector Hochiki CDXFixed-temperature heat detector 60 °C DFJ-AE3 (conventional)NSC B03015-00yessame typeno
Heat detector Hochiki CDXFixed-temperature heat detector 90 °C DFJ-CE3 (conventional)NSC B03020-00yessame typeno
Heat detector Hochiki CDXMulti-heat detector 60 °C DCD-AE3 (conventional)NSC B03025-00yessame typeno
Heat detector Hochiki CDXMulti-heat detector 90 °C DCD-CE3 (conventional)NSC B03030-00yessame typeno
Heat detector Hochiki CDXFixed-temperature heat detector 60 °C DFG-60BLKJ, IP67 (conventional)NSC B03050-00yessame typeno

Variants in black (BLK) and with SIL or marine approval are also available – please specify when making your enquiry.

Bases

Hochiki bases at NSC: when a new base is needed

The standard base remains when the detector is replaced. A new base is only needed if you switch to detectors using a different technology – for example from conventional (CDX) to addressable loop (ESP).

ImageBasesItem no. (NSC)Suitable forNote
Detector base Hochiki YBN-R/3Standard mounting base YBN-R/3, whiteNSC B02200-00ESP addressable loop detectorsremains during replacement
Detector base Hochiki YBN-R/3Mounting base YBN-R/3 SCI with dual isolatorNSC B02220-00ESP addressable loop detectorsremains during replacement
Detector base Hochiki YBN-R/3Mounting base YBV-R/4 (ESP Top Loop)NSC B02222-00ESP Top Loop detectorsremains during replacement
Detector base Hochiki YBN-R/6Standard mounting base YBN-R/6NSC B03100-00CDX conventional detectorsremains during replacement
Detector base Hochiki YBN-R/6Relay base YBO-R/6RN, non-latchingNSC B03107-00CDX conventional detectorsremains during replacement
Detector base Hochiki YBN-R/6Relay base YBO-R/6R, latchingNSC B03109-00CDX conventional detectorsremains during replacement

No longer available

Apollo detectors (NSC, Labor Strauss, MEP, Hertek): replacing older types

Ionisation detectors of the Apollo series XP95 and Discovery have been discontinued. This affects systems from NSC as well as from Labor Strauss, MEP-Gefahrenmeldetechnik and Hertek. According to NSC, the successor Soteria is backward compatible with XP95 and Discovery (protocol and base) – the existing base 45681-210 remains. Conventional detectors of the older Series 60 can be replaced by Series 65 or, using the adapter B04500-00, by Orbis detectors on the existing base.

Apollo XP95, Discovery and Series 60

ImageOld detectorOld manufacturer’s codeAvailable?Alternative detector (NSC item no. / manufacturer’s code)New base?
Detector Apollo XP95Ionisation smoke detector XP9555000-500no – discontinuedSoteria Multisensor (NSC B02904-00 / SA5100-700)¹no – 45681-210 remains
Detector Apollo DiscoveryIonisation smoke detector Discovery58000-500no – discontinuedSoteria Multisensor (NSC B02904-00 / SA5100-700)¹no – 45681-210 remains
Detector Apollo Series 65Optical smoke detector Series 60 (conventional)see rating plateno – discontinuedS65 optical smoke detector (NSC B03570-00 / 55000-317) or Orbis with adapter³no – base remains; for Orbis, adapter B04500-00
Detector Apollo Series 65Heat detector Series 60 (conventional)see rating plateno – discontinuedS65 heat detector of the appropriate class, e.g. A1R (NSC B03576-00 / 55000-122)³no – base remains

¹ Ionisation detectors are no longer manufactured. Which detector replaces them depends on the fire detection and alarm concept – we agree this with you. Soteria requires your control panel to support the detector; we check this in advance. ³ According to NSC, the adapter B04500-00 (ORB-BA-10008) allows Orbis detectors to be used on S60/S65 bases. The heat class depends on the place of installation.

Current series

Apollo Soteria, Discovery, XP95, Orbis and Series 65: same detector, same base

These Apollo detectors are currently available – equally for NSC, Labor Strauss, MEP and Hertek systems; the item number refers to NSC, while the manufacturer’s code applies across all suppliers. When replaced on schedule, the detector is exchanged for the same type and the existing base remains. For XP95 and Discovery systems, Soteria is the recommended successor.

ImageDetectorsItem no. (NSC / manufacturer’s code)Available?Replace withNew base?
Optical detector Apollo SoteriaOptical addressable loop detector SoteriaNSC B02900-00 / SA5100-600yessame typeno – 45681-210 remains
Multi-sensor detector Apollo SoteriaMulti-sensor addressable loop detector Soteria (O/T)NSC B02904-00 / SA5100-700yessame typeno
Multi-sensor detector Apollo SoteriaMulti-sensor addressable loop detector Soteria Dual OpticalNSC B02908-00 / SA5100-710yessame typeno
Multi-sensor detector Apollo SoteriaTri-sensor detector Soteria Dual Optical + CONSC B02910-00 / SA5100-810yessame typeno
Heat detector Apollo SoteriaMulti-heat addressable loop detector SoteriaNSC B02906-00 / SA5100-400yessame typeno
Detector Apollo DiscoveryOptical addressable loop detector DiscoveryNSC B02700-00 / 58000-600yessame type or Soteria (B02900-00)no – 45681-210 remains
Detector Apollo DiscoveryMulti-sensor addressable loop detector Discovery (O/T)NSC B02704-00 / 58000-700yessame type or Soteria (B02904-00)no
Detector Apollo DiscoveryAddressable loop heat detector DiscoveryNSC B02706-00 / 58000-400yessame type or Soteria (B02906-00)no
Detector Apollo DiscoveryCO addressable loop detector DiscoveryNSC B02708-00 / 58000-300yessame typeno
Detector Apollo DiscoveryMulti-sensor addressable loop detector Discovery (CO/T)NSC B02710-00 / 58000-305yessame typeno
Detector Apollo XP95Optical addressable loop detector XP95NSC B02600-00 / 55000-620yessame type or Soteria (B02900-00)no – 45681-210 remains
Detector Apollo XP95Addressable loop heat detector XP95 A2S (55 °C)NSC B02606-00 / 55000-420yessame type or Soteria (B02906-00)no
Detector Apollo XP95Addressable loop heat detector XP95 A2S (55 °C), variantNSC B02607-00 / 55000-400yessame typeno
Detector Apollo XP95Addressable loop heat detector XP95 CS (90 °C)NSC B02608-00 / 55000-401yessame typeno
Detector Apollo OrbisOptical smoke detector Orbis (conventional)NSC B03540-00 / ORB-OP-12001yessame typeno – Orbis base remains
Detector Apollo OrbisMulti-sensor Orbis O/T (conventional)NSC B03542-00 / ORB-OH-13001yessame typeno
Detector Apollo OrbisHeat detector Orbis A1R (57 °C)NSC B03544-00 / ORB-HT-11001yessame typeno
Detector Apollo OrbisFixed-temperature heat detector Orbis A1S (57 °C)NSC B03546-00 / ORB-HT-11166yessame typeno
Detector Apollo OrbisFixed-temperature heat detector Orbis A2S (61 °C)NSC B03548-00 / ORB-HT-11002yessame typeno
Detector Apollo OrbisHeat detector Orbis BR (73 °C)NSC B03550-00 / ORB-HT-11003yessame typeno
Detector Apollo OrbisFixed-temperature heat detector Orbis BS (73 °C)NSC B03552-00 / ORB-HT-11004yessame typeno
Detector Apollo OrbisHeat detector Orbis CR (90 °C)NSC B03554-00 / ORB-HT-11005yessame typeno
Detector Apollo OrbisFixed-temperature heat detector Orbis CS (90 °C)NSC B03556-00 / ORB-HT-11006yessame typeno
Detector Apollo Series 65Optical smoke detector Series 65 (conventional)NSC B03570-00 / 55000-317yessame typeno – S65 base remains
Detector Apollo Series 65Heat detector Series 65 A1RNSC B03576-00 / 55000-122yessame typeno
Detector Apollo Series 65Heat detector Series 65 BRNSC B03578-00 / 55000-127yessame typeno
Detector Apollo Series 65Heat detector Series 65 CRNSC B03580-00 / 55000-132yessame typeno
Detector Apollo Series 65Fixed-temperature heat detector Series 65 CSNSC B03582-00 / 55000-137yessame typeno

Variants with flashing LED, in black or with SIL2 approval are also available – please specify when making your enquiry.

Bases

Apollo bases (NSC, Labor Strauss, MEP, Hertek): when a new base is needed

Apollo bases are used equally by NSC, Labor Strauss, MEP-Gefahrenmeldetechnik and Hertek. XP95, Discovery and Soteria detectors fit the same loop base; Orbis and Series 65 have their own conventional bases. A new base is only needed when changing technology (conventional ↔ addressable loop).

ImageBasesItem no. (NSC / manufacturer’s code)Suitable forNote
Detector base Apollo XP95/DiscoveryLoop detector base XP95/Discovery (with XPERT7 card)NSC B02750-00 / 45681-210XP95, Discovery, Soteriaremains during replacement
Detector base Apollo XP95/DiscoveryDetector base with isolator XP95/DiscoveryNSC B02752-00 / 45681-284XP95, Discoveryremains during replacement
Detector base Apollo SoteriaSoteria XPERT8 standard baseNSC B02950-00 / SA5000-200Soteria, XP95, Discoveryfor new installations; existing 45681-210 bases remain
Detector base Apollo OrbisOrbis TimeSaver baseNSC B03558-00 / ORB-MB-00001Orbisremains during replacement
Detector base Apollo OrbisOrbis relay baseNSC B03560-00 / ORB-RB-10004Orbisremains during replacement
Detector base Apollo Series 65Standard base Series 65NSC B03584-00 / 45681-200Series 60/65remains during replacement
Detector base Apollo Series 65Relay base Series 65NSC B03586-00 / 45681-245Series 65remains during replacement
Detector base Apollo Series 65Adapter Orbis to S65 baseNSC B04500-00 / ORB-BA-10008Orbis detectors on S60/S65 basesinstead of base replacement

Special detectors

NSC (Hochiki / Apollo): wireless, Ex, duct and linear detectors

For special applications, NSC distributes wireless detectors from Apollo, aspirating smoke detectors from Stratos and linear beam smoke detectors. We coordinate Ex, duct and linear detectors from Hochiki or Apollo individually with NSC, as the dealer price list is not public.

ImageDetectorsItem no.Available?Replace withNote
–Apollo XPander wireless optical smoke detector incl. base (wireless extension for XP95/Discovery loop, EN 54-25)XPA-CB-12034-APOyessame type; batteries according to manufacturer’s specificationsvia XPander Loop Interface
–Aspirating smoke detector Stratos HSSD 2, Micra, ModuLaser (EN 54-20)see Stratos pageyesDetector chamber as specified by the manufacturerConnection via APIC card Hochiki/Apollo
–Linear beam smoke detectors (e.g. Fireray, FIREBEAM) and Ex detectors for Hochiki/Apollo loopson requestyessame typevia input/output module or Ex barrier

We will give you the NSC order numbers with the quote.

Important

Before ordering

  • Check the panel: Whether Hochiki or Apollo detectors can be operated on your fire alarm control panel (NSC Solution F1/F2, Labor Strauss, MEP or Hertek) depends on the panel, protocol and programming. We check this using your detector list and programming file.
  • Replacement interval: Smoke and multi-sensor detectors after 5 years at the latest, or after 8 years with automatic contamination compensation and testing in accordance with the manufacturer’s specifications – details under Deadlines & standards.
  • Change of detector series: New bases, different detector types or a changed number of detectors may constitute a significant modification – see expert inspection and fire brigade.
  • EN 54 tested (as of 19.10.2026): All Hochiki (ESP, CDX) and Apollo detectors (Soteria, Discovery, XP95, Orbis, Series 65) listed as available are certified to EN 54-5 or EN 54-7, detectors with isolator additionally to EN 54-17. The detectors that are no longer available were approved under the EN 54 or VdS rules applicable when they were introduced; since 2008, CE marking to EN 54 has been mandatory for new detectors – which is why we only list currently certified types as replacements.
  • Installation by a specialist company only: Replacement and repair of detectors in fire alarm systems required under building law are part of maintenance and are reserved for a specialist company certified to DIN 14675 – even if you only buy the detectors from us. Details under Legal situation.
  • Order numbers are NSC item numbers and Apollo manufacturer’s codes (source: shop.nsc-sicherheit.de, last updated: 18.10.2026).
  • Image credits and trademarks: Product images © NSC Sicherheitstechnik, Hochiki or Apollo Fire Detectors. The images serve solely to identify the detectors. Brand and product names are the property of their respective owners. Further information in the Legal notice.

Not sure which detector is installed at your site?

Send us your detector list or a photo of the type plate. We will name the suitable replacement and tell you whether new bases are needed.