Detectors

Replacing ESSER detectors: types, successors and bases

Which ESSER detectors from year of manufacture 2000 onwards must be replaced, what is still available, which detector replaces older types and when a new base is needed – with the manufacturers’ order numbers.

← All manufacturers at a glance

Detector age

How old is the detector – how long has it been in operation?

  • ESSER: Type plate with article number, serial number and date of manufacture. According to Honeywell, IQ8Quad detectors store alarm and operating data in the detector. On IQ8Control and FlexES Control, the detector data of IQ8Quad and ES Detect detectors (including contamination level) can be retrieved via the operating unit or tools 8000. On aspirating smoke detectors, the date is on the detector module.
  • Logbook and reports (decisive): The operating time counts from the commissioning of the detector. The date is recorded in the logbook, in the commissioning or acceptance report or in the last replacement report. This gives the years and months in operation.
  • Type plate on the detector: The label (usually on the underside or side of the detector, visible after twisting it out of the base) shows the type, serial number and date of manufacture or a date code (e.g. year/calendar week). If no commissioning date is documented, we take the cautious approach of calculating from the date of manufacture.
  • Reading out via the panel: With many addressable loop detectors, detector data such as serial number, date of manufacture, degree of contamination and – depending on the system and software version – operating hours can be retrieved via the panel’s operating unit or programming software. We do this during the survey using your programming file.

This determines the replacement interval under DIN 14675: as a rule 5 years, or 8 years for detectors with contamination compensation and testing in accordance with the manufacturer’s specifications – details under Deadlines & standards. Send us a photo of the type plate and we will determine the age for you.

Identify

Which ESSER detector do you have installed?

The images show the current ESSER designs. Within a series, many types look the same – what matters is the article number. It is on the type plate on the detector (usually on the back or on the edge of the detector) and on the base. It also tells you the series: 76xxxx / 78xxxx = Series 9000, 801xxx = Series 9200, 802xxx / 803xxx = IQ8Quad, 800xxx = ES Detect.

Images: Honeywell / ESSER. Examples shown; housing colour and labelling may differ depending on the type.

No longer available

Series 9000 and Series 9200: replacing detectors and bases

The conventional detectors of Series 9000 and the analogue detectors of Series 9200 were manufactured until roughly the mid-2000s and are no longer available. Smoke and multi-sensor detectors of these series have in any case exceeded the replacement interval under DIN 14675-1. The successors do not fit into the old bases (7814xx / 7815xx / 801593) – a new base is always required.

Series 9000 (conventional technology) → ES Detect

ImageOld detectorOld item no.Available?Alternative detector (item no.)New base?
ESSER detectors of the older Series 9000 / 9200Ionisation smoke detector Series 9000761062 / 781062no – discontinued800374 O²T multi-sensor detector ES Detect¹yes: 805590
ESSER detectors of the older Series 9000 / 9200Fixed-temperature heat detector 58 °C Series 9000761162 / 781162no – discontinued800171 Fixed-temperature heat detector ES Detectyes: 805590
ESSER detectors of the older Series 9000 / 9200Fixed-temperature heat detector 82 °C Series 9000761167 / 781167no – discontinued800177 Fixed-temperature heat detector ES Detect, class B²yes: 805590
ESSER detectors of the older Series 9000 / 9200Rate-of-rise heat detector Series 9000761262 / 781262no – discontinued800271 Rate-of-rise heat detector ES Detectyes: 805590
ESSER detectors of the older Series 9000 / 9200Optical smoke detector Series 9000761362 / 781362no – discontinued800371 Optical smoke detector ES Detect
or 800375 OTblue / 800374 O²T
yes: 805590

Series 9200 (analogue technology) → IQ8Quad

ImageOld detectorOld item no.Available?Alternative detector (item no.)New base?
ESSER detectors of the older Series 9000 / 9200Ionisation smoke detector Series 9200801071no – discontinued802374 O²T multi-sensor detector IQ8Quad¹yes: 805590
ESSER detectors of the older Series 9000 / 9200Fixed-temperature heat detector Series 9200801171no – discontinued802171 Fixed-temperature heat detector IQ8Quadyes: 805590
ESSER detectors of the older Series 9000 / 9200Rate-of-rise heat detector Series 9200801271no – discontinued802271 Rate-of-rise heat detector IQ8Quadyes: 805590
ESSER detectors of the older Series 9000 / 9200Optical smoke detector Series 9200801371no – discontinued802371 Optical smoke detector IQ8Quadyes: 805590
ESSER detectors of the older Series 9000 / 9200OT multi-sensor detector Series 9200801373no – discontinued802373 OT or 802375 OTblue IQ8Quadyes: 805590
ESSER detectors of the older Series 9000 / 9200O²T multi-sensor detector Series 9200801374no – discontinued802374 O²T multi-sensor detector IQ8Quadyes: 805590
ESSER detectors of the older Series 9000 / 9200OTI multi-sensor detector Series 9200801973no – discontinued802374 O²T or 802473 OTG (CO) IQ8Quad¹yes: 805590
–IQ8Quad Ex (i) optical smoke detector for hazardous (Ex) areas803371.EXno – discontinued according to Honeywellno direct successor in the ESSER range – solution on request (e.g. Ex detector with barrier)on request
–Ex detector Series 9100 (intrinsically safe, with Ex barrier Z969)see rating plateno – discontinuedSolution on requeston request

¹ Ionisation and OTI detectors are no longer manufactured. Which detector replaces them depends on the fire detection and alarm concept – we will agree this with you. ² Class B according to EN 54-5; please check the response temperature at the place of use.

Current series

IQ8Quad and ES Detect: same detector, same base

Detectors of the IQ8Quad (analogue technology, esserbus) and ES Detect (conventional technology) series are still available. When replaced in accordance with the deadline, the detector is exchanged for the same type and the existing base 805590 or 805591 remains. For IQ8Quad there are also self-test detectors (-ST), which make on-site function testing easier.

ImageDetectorsItem no.Available?Replace withNew base?
Heat detector IQ8QuadFixed-temperature heat detector IQ8Quad802171yessame typeno – 805590 remains
Heat detector IQ8QuadFixed-temperature heat detector IQ8Quad, class B802177yessame typeno
Heat detector IQ8QuadRate-of-rise heat detector IQ8Quad802271yessame type or 802271-ST self-testno
Smoke/multi-sensor detector IQ8QuadOptical smoke detector IQ8Quad802371yessame type or 802371-ST self-testno
Smoke/multi-sensor detector IQ8QuadOT multi-sensor detector IQ8Quad802373yessame type or 802373-ST self-testno
Smoke/multi-sensor detector IQ8QuadO²T multi-sensor detector IQ8Quad802374yessame type or 802374-ST self-testno
Smoke/multi-sensor detector IQ8QuadOTblue multi-sensor detector IQ8Quad802375yessame type or 802375-ST self-testno
OTG multi-sensor detector IQ8QuadOTG multi-sensor detector (CO) IQ8Quad802473yessame typeno
IQ8Quad with sounderIQ8Quad O/So (optical, with sounder)802382yessame type or self-test variant (-ST)no – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/F (with flashing beacon)802383yessame type or self-test variant (-ST)no – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/So (with sounder)802384yessame type or self-test variant (-ST)no – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/FSp (with flashing beacon and voice output)802385yessame type or self-test variant (-ST)no – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/Sp (with voice output)802386yessame type or self-test variant (-ST)no – not in relay base 805591
Heat detector IQ8QuadFixed-temperature heat detector IQ8Quad without isolator (FSA)803171yessame typeno
Heat detector IQ8QuadRate-of-rise heat detector IQ8Quad without isolator (FSA)803271yessame typeno
Smoke/multi-sensor detector IQ8QuadOptical smoke detector IQ8Quad without isolator (FSA)803371yessame typeno
Smoke/multi-sensor detector IQ8QuadO²T multi-sensor detector IQ8Quad without isolator (FSA)803374yessame typeno
Heat detector ES DetectFixed-temperature heat detector ES Detect800171yessame typeno – 805590 remains
Heat detector ES DetectFixed-temperature heat detector ES Detect, class B800177yessame typeno
Heat detector ES DetectRate-of-rise heat detector ES Detect800271yessame typeno
Smoke/multi-sensor detector ES DetectOptical smoke detector ES Detect800371yessame typeno
Smoke/multi-sensor detector ES DetectO²T multi-sensor detector ES Detect800374yessame typeno
Smoke/multi-sensor detector ES DetectOTblue multi-sensor detector ES Detect800375yessame typeno

IQ8Quad self-test detectors (-ST)

The self-test detectors of the IQ8Quad series test their sensors automatically, making on-site maintenance easier. They have only been in use for a few years – replacement is expected to be due from approx. 2033 at the earliest. They are replaced with the same type; the base 805590 remains.

ImageDetectorsItem no.Available?Replace withNew base?
Heat detector IQ8QuadRate-of-rise heat detector IQ8Quad self-test802271-STyessame typeno – 805590 remains
Smoke/multi-sensor detector IQ8QuadOptical smoke detector IQ8Quad self-test802371-STyessame typeno
Smoke/multi-sensor detector IQ8QuadOT multi-sensor detector IQ8Quad self-test802373-STyessame typeno
Smoke/multi-sensor detector IQ8QuadO²T multi-sensor detector IQ8Quad self-test802374-STyessame typeno
Smoke/multi-sensor detector IQ8QuadOTblue multi-sensor detector IQ8Quad self-test802375-STyessame typeno
IQ8Quad with sounderIQ8Quad O/So self-test (optical, with sounder)802382-STyessame typeno – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/F self-test (with flashing beacon)802383-STyessame typeno – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/So self-test (with sounder)802384-STyessame typeno – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/FSp self-test (with flashing beacon and voice output)802385-STyessame typeno – not in relay base 805591
IQ8Quad with sounderIQ8Quad O²T/Sp self-test (with voice output)802386-STyessame typeno – not in relay base 805591

Bases

Which new base replaces the old one?

ImageOld baseOld item no.New base (item no.)
Detector base ESSER Series 9000 / 9200Standard base Series 9000 / 9200781490 / 781590Detector base standard 805590
805590 Detector base standard
Detector base ESSER Series 9000 / 9200Base with relay output Series 9000781488 / 781588Detector base with relay 805591
805591 Detector base with relay contact (24 V)
or 805592 for 48 V systems (ES Detect only)
Detector base ESSER Series 9000 / 9200Base with relay output Series 9200781491 / 781591Detector base with relay 805591
805591 Detector base with relay contact³
Detector base ESSER Series 9000 / 9200Base with optocoupler output781492 / 781592no direct successor – solution on request
Detector base ESSER Series 9000 / 9200Base with isolator Series 9200781493 / 781593 / 801493 / 801593Detector base standard 805590
805590 – the isolator is integrated in the IQ8Quad detector

³ The relay base 805591 is not suitable for IQ8Quad detectors with integrated sounder (802382 to 802386).

aspirating smoke detectors (ASD)

ESSER aspirating smoke detectors on the esserbus

ESSER offers aspirating smoke detectors with an integrated esserbus coupler: TITANUS EB (WAGNER technology), FAAST LT EB and VESDA-E EBTI (Xtralis/Honeywell technology). They run directly on the esserbus or esserbus-PLus loop and are programmed with tools 8000. All devices are tested to EN 54-20. When replaced in accordance with the deadline under DIN 14675, the detector module or the replacement detector is exchanged – not the base unit.

No longer in the ESSER range

ImageOld unitOld item no.Available?AlternativeNew pipe network?
TITANUS PRO SENS EBCompact unit TITANUS PRO SENS EB (with detector module)801515.10no – no longer in the catalogueBase unit TITANUS PRO SENS 2 EB (801522.10) + detector moduleaccording to system design¹
TITANUS PRO SENS EBBase unit TITANUS PRO SENS EB (1 pipe)801521.10no – no longer in the catalogueBase unit TITANUS PRO SENS 2 EB (801522.10)according to system design¹
TITANUS TOP SENS EBBase unit TITANUS TOP SENS 1 EB / EB.SL (low-noise fan)801531.10 / 801531.10.SLno – no longer in the catalogueTITANUS PRO SENS 2 EB, FAAST LT-200 EB or VESDA-E EBTIaccording to system design¹
TITANUS TOP SENS EBBase unit TITANUS TOP SENS 2 EB (2 pipes)801532.10no – no longer in the catalogueTITANUS PRO SENS 2 EB, FAAST LT-200 EB 2 or VESDA-E EBTIaccording to system design¹
TITANUS PRO SENS EBDetector module DM-TP-50-LE (TITANUS PRO SENS EB)801523.10no – no longer in the catalogueDM-TP-10L (801524.10) according to system designaccording to system design¹
TITANUS TOP SENS EBDetector modules DM-TT-50-LE / DM-TT-10-LE / DM-TT-01-LE (TITANUS TOP SENS EB)801533.10 / 801534.10 / 801535.10no – no longer in the catalogueChangeover to current unitaccording to system design¹

Current ESSER aspirating smoke detectors

ImageUnitItem no.Available?Replaced partNote
TITANUS PRO SENS EBBase unit TITANUS PRO SENS 2 EB, 2 pipes, with esserbus coupler (VdS G 206118)801522.10yesdetector moduleesserbus coupler 808623 integrated
TITANUS PRO SENS EBDetector module 0.10 %/m, type DM-TP-10L801524.10yessame typefor TITANUS PRO SENS EB
TITANUS PRO SENS EBDetector module 0.015 %/m, type DM-TP-01L801525.10yessame typefor TITANUS PRO SENS EB
–FAAST LT-200 EB, 1 channel, loop-capable801711.10yesReplacement detector F-SEN-SSEReplacement filter FL-IF-2
–FAAST LT-200 EB 2, 2 channels, loop-capable801722.10yesReplacement detector F-SEN-SSEReplacement filter FL-IF-2
–FAAST FLEX, 1 pipe or 2 pipes, with relayFLX-010 / FLX-020yesaccording to manufacturer’s specificationsConnection via relay / coupler
VESDA-E esserbusVESDA-E VEU with LEDs, esserbusVEU-A00-EBTIyesaccording to manufacturer’s specificationsup to 4 status messages via esserbus
VESDA-E esserbusVESDA-E VEP 4 pipes with 3.5″ display, esserbusVEP-A10-P-EBTIyesaccording to manufacturer’s specificationson IQ8Control without pre-alarm
VESDA-E esserbusVESDA-E VEP single pipe with LEDs, esserbusVEP-A00-1P-EBTIyesaccording to manufacturer’s specifications–
VESDA-E esserbusVESDA Laser Industrial with VESDAnetVLI-885yesaccording to manufacturer’s specificationsConnection via interface

Article numbers according to the online ESSER product catalogue (esser-systems.com) and ESSER product information 795810 (05/2011). ¹ When changing the base unit, or changing to a detector module with a different sensitivity, the pipe network must be recalculated in accordance with EN 54-20; this is generally a significant modification. Further VESDA types can be found on the Xtralis page, TITANUS detector modules on the WAGNER page.

Special detectors

ESSER: wireless, Ex, duct and linear detectors

In addition to IQ8Quad and ES Detect, ESSER offers wireless detectors (IQ8Wireless), Ex detectors, duct detectors and linear beam smoke detectors. Aspirating smoke detectors can be found in the section above.

ImageDetectorsItem no.Available?Replace withNote
IQ8Wireless radio baseIQ8Wireless radio base – turns an IQ8Quad detector into a wireless detector (EN 54-25)805593.10yesDetector in the radio base with the same IQ8Quad type; batteries as specified by the manufacturerRadio base remains
IQ8Wireless radio gatewayIQ8Wireless radio gateway for detectors (connection to the esserbus)805594.10yes–Gateway remains
–Optical Ex smoke detector IQ8Quad Ex (i)803371.EXno – discontinuedsee table “No longer available”Ex barrier Z969
FSL100Ex flame detectors FSL100-IR3 (triple IR), FSL100-UV and FSL100-UVIR (EN 54-10, ATEX)FSL100-IR3 / -UV / -UVIRyessame typeBracket FSL100-SM21
–UniVario flame detector UV or triple IR (EN 54-10)782311 / 782315yessame typeBase UniVario 783313
Duct detector kitDuct detector kit for IQ8Quad or ES Detect smoke detectors781463yesinserted smoke detector according to deadlinehousing and tube remain
LRMXLinear beam smoke detector LRMX (EN 54-12)761400.10yessame typeReflector remains
LRMX heatingLRMX with anti-fogging and heating (EN 54-12)761410yessame type–
LRMX blueLRMX blue with app control (EN 54-12)761423yessame type–
–OSID imaging linear beam smoke detector – receiver 7° / 80°, light sources standard/high power (EN 54-12)OSI-10 / OSI-90 / OSE-SPW / OSE-HPWyessame type–
–Conventional linear beam smoke detector OSI-RE (EN 54-12)OSI-REyessame type–

Article numbers according to the online ESSER product catalogue (esser-systems.com, as of 10/2026). Wireless detectors: battery replacement as specified by the manufacturer; linear beam smoke detectors and flame detectors are inspected as specified by the manufacturer.

Important

Before ordering

  • Check the panel: Whether IQ8Quad or ES Detect detectors can be operated on your fire alarm control panel depends on the panel, loop or line technology and programming. We check this using your detector list and programming file.
  • Replacement interval: Smoke and multi-sensor detectors after 5 years at the latest, or after 8 years with automatic contamination compensation and testing in accordance with the manufacturer’s specifications – details under Deadlines & standards.
  • Change of detector series: New bases, different detector types or a changed number of detectors may constitute a significant modification – see expert inspection and fire brigade.
  • EN 54 tested (as of 19.10.2026): All IQ8Quad, ES Detect and self-test detectors listed as available are certified to EN 54-5 (heat) or EN 54-7 (smoke), those with integrated isolator also to EN 54-17 and those with sounder/flashing beacon additionally to EN 54-3/-23; the aspirating smoke detectors to EN 54-20. Exception: the IQ8Quad Ex (i) has been discontinued; for hazardous (Ex) areas, the replacement must be clarified individually. The detectors that are no longer available were approved under the EN 54 or VdS rules applicable when they were introduced; since 2008, CE marking according to EN 54 has been mandatory for new detectors – which is why we only list currently certified types as replacements.
  • Installation by a specialist company only: Replacement and repair of detectors in fire alarm systems required under building law are part of maintenance and are reserved for a specialist company certified to DIN 14675 – even if you only buy the detectors from us. Details under Legal situation.
  • Order numbers are the article numbers of the manufacturer ESSER by Honeywell (last updated: 18.10.2026, source: esser-systems.com). The links lead to the manufacturer’s product search.
  • Image credits and trademarks: Product images © Honeywell / ESSER. The images serve solely to identify the detectors. Brand and product names are the property of their respective owners. Further details in the Legal notice.