Detectors
Replacing Detectomat detectors: types, successors and bases
Which Detectomat detectors manufactured from 2000 onwards must be replaced, what is still available, which detector replaces older types and when a new base is needed – with the manufacturers’ order numbers.
Detector age
How old is the detector – how long has it been in operation?
- Detectomat: Rating plate with item number and date of manufacture or date code. The commissioning date can be found in the logbook and records.
- Logbook and reports (decisive): The operating time counts from the commissioning of the detector. The date is recorded in the logbook, in the commissioning or acceptance report or in the last replacement report. This gives the years and months in operation.
- Type plate on the detector: The label (usually on the underside or side of the detector, visible after twisting it out of the base) shows the type, serial number and date of manufacture or a date code (e.g. year/calendar week). If no commissioning date is documented, we take the cautious approach of calculating from the date of manufacture.
- Reading out via the panel: With many addressable loop detectors, detector data such as serial number, date of manufacture, degree of contamination and – depending on the system and software version – operating hours can be retrieved via the panel’s operating unit or programming software. We do this during the survey using your programming file.
This determines the replacement interval under DIN 14675: as a rule 5 years, or 8 years for detectors with contamination compensation and testing in accordance with the manufacturer’s specifications – details under Deadlines & standards. Send us a photo of the type plate and we will determine the age for you.
Identify
Which Detectomat detector do you have installed?
Detectomat detectors are available as addressable loop detectors for the system Loop3000 (type designation PL 3200 … or PL 3300 …, control panels e.g. dc3500) and as conventional detectors of the series CT 3000. The type designation and the five-digit item number are shown on the rating plate on the detector. Since 2025, several detectors have been available in a new “Version 2025” with a new item number – according to Detectomat, 100% compatible with the predecessor.








Images: Detectomat. Examples shown; housing colour and labelling may vary by type.
No longer available
Older Detectomat detectors: successors and bases
The addressable loop detectors of the PL 3200 series have been discontinued and are being replaced by the PL 3300 series. For the PL 3300 and CT 3000 series, Detectomat replaced several detectors in 2025 with a new version with a new item number – according to Detectomat 100% compatible; the base remains.
Loop3000 (addressable loop) and CT 3000 (conventional)
| Image | Old detector | Old item no. | Available? | Alternative detector (item no.) | New base? |
|---|---|---|---|---|---|
![]() | Optical smoke detector PL 3200 O | 30009 | no – discontinued | PL 3300 O, Version 2025 (33974)² | on request² |
![]() | Heat detector PL 3200 T | 30008 | no – discontinued | PL 3300 T, Version 2025 (33982)² | on request² |
![]() | Multi-sensor detector PL 3200 OT | 30007 | no – discontinued | PL 3300 OTi, Version 2025 (33990)² | on request² |
![]() | Optical smoke detector PL 3300 O | 30011 | no – replaced | PL 3300 O, Version 2025 (33974)¹ | no – base remains |
![]() | Heat detector PL 3300 T | 30010 | no – replaced | PL 3300 T, Version 2025 (33982)¹ | no – base remains |
![]() | Multi-sensor detector PL 3300 OT | 30021 | no – discontinued | PL 3300 OTi, Version 2025 (33990)² | no – base remains |
![]() | Multi-sensor detector PL 3300 OTi | 32150 | no – replaced | PL 3300 OTi, Version 2025 (33990)¹ | no – base remains |
![]() | Optical smoke detector CT 3000 O (conventional) | 30015 | no – replaced | CT 3000 O, Version 2025 (33978) | no – SDB 3000 remains |
![]() | Heat detector CT 3000 T (conventional, A1) | 30014 | no – replaced | CT 3000 T, Version 2025 (33986) | no – SDB 3000 remains |
¹ According to Detectomat, a “100% compatible replacement” for the previous item. ² Successor from the PL 3300 series; we check using your detector list whether the control panel works without reprogramming and whether the existing base can continue to be used.
Current series
Loop3000 and CT 3000: same detector, same base
These Detectomat detectors are available. When replaced on schedule, the detector is exchanged for the same type and the existing base remains.
| Image | Detectors | Item no. | Available? | Replace with | New base? |
|---|---|---|---|---|---|
![]() | Optical smoke detector with isolator PL 3300 O, Version 2025 | 33974 | yes | same type | no – SDBB 3000 remains |
![]() | Heat detector with isolator PL 3300 T, Version 2025 | 33982 | yes | same type | no |
![]() | Multi-sensor detector with isolator PL 3300 OTi, Version 2025 | 33990 | yes | same type | no |
![]() | Multi-sensor detector with isolator PL 3300 OTi, black | 34212 | yes | same type | no |
![]() | Multi-sensor detector with isolator PL 3300 OTi Fusion (two optical and two heat sensors) | 32149 | yes | same type | no |
![]() | CO multi-sensor detector with isolator PL 3300 COBT | 30079 | yes | same type | no |
![]() | Optical smoke detector CT 3000 O, Version 2025 (conventional) | 33978 | yes | same type | no – SDB 3000 remains |
![]() | Heat detector CT 3000 T, Version 2025 (conventional, A1S/A1R/A2S/A2R) | 33986 | yes | same type | no |
![]() | Multi-sensor detector CT 3000 OT (conventional) | 30022 | yes | same type | no |
![]() | Multi-sensor detector CT 3000 OTi, Version 2025 (conventional) | 33994 | yes | same type | no |
![]() | Heat detector TRC05 (conventional, A1R) | 40290 | yes | same type | on request |
![]() | Heat detector TSC05-A1S, fixed-temperature 75 °C (conventional) | 40295 | yes | same type | on request |
![]() | Heat detector TSC05-BS, fixed-temperature 75 °C (conventional) | 40298 | yes | same type | on request |
Bases
Detectomat bases: when a new base is needed
According to Detectomat, the base SDB 3000 fits all detectors of the CT and Loop3000 series; the base SDBB 3000 additionally has a bridge that keeps the loop closed when the detector is removed. When the detector is replaced with the same type or the Version 2025, the base remains.
| Image | Bases | Item no. | Suitable for | Note |
|---|---|---|---|---|
![]() | Detector base SDB 3000, white | 30301 | all detectors of the CT and Loop3000 series | remains during replacement |
![]() | Detector base SDBB 3000, white (with bridge) | 31959 | all detectors of the Loop3000 series | remains during replacement |
![]() | Detector base SDBB 3000 S, white (with bridge) | 32241 | all detectors of the Loop3000 series | remains during replacement |
![]() | Heated surface-mounted base APS b | 31875 | Detectors of the CT and Loop3000 series | for damp, temperature-critical areas |
![]() | Adapter base DAB 3000 (surface-mounted/damp rooms) | 32444 | all Detectomat detector bases | Accessories |
![]() | Adapter base DAB basic, without cable glands | 32779 | all detector bases | Accessories |
Special detectors
Detectomat: wireless, Ex, duct and linear detectors
For hazardous (Ex) areas, ventilation ducts, large halls and open-flame fires, Detectomat offers special detectors. Wireless detectors are not included in the current Detectomat catalogue.
| Image | Detectors | Item no. | Available? | Replace with | Note |
|---|---|---|---|---|---|
![]() | Intrinsically safe optical Ex smoke detector (conventional) for ALPHA or DC3500 via TCM module (EN 54-7, ATEX) | 40202 | yes | same type | Ex base S05EX (40236) remains |
![]() | Intrinsically safe Ex heat detector A1R (EN 54-5, ATEX) | 40292 | yes | same type | Ex base S05EX (40236) remains |
![]() | Intrinsically safe IR flame detector, Ex, conventional, Zone 0 (ATEX) | 40307 | yes | same type | via Ex barrier SBEx BZ1 |
![]() | Linear beam Ex smoke detector (IR short beam) with relay contacts, 3–30 m (EN 54-12, ATEX Ex d) | 40087 | yes | same type | – |
![]() | Duct detector housing with sampling/exhaust tube for PL 3300 O/K detectors, ducts up to 500 mm | 40064 | yes | inserted detector according to replacement interval | housing remains |
![]() | Linear beam smoke detector DLF150 with relay, 8–150 m (EN 54-12, VdS G 226040) | 34108 | yes | same type | Extension kits 33642 / 33644 |
![]() | DLF150 with relay and integrated heater (EN 54-12, VdS G 226040) | 34109 | yes | same type | – |
![]() | UV flame detector FMX 5000 UV (EN 54-10, VdS G 221017) | 32272 | yes | same type | Relay module KMX5000 RK (32928) |
![]() | IR flame detector FMX5000 IR (EN 54-10) | 32911 | yes | same type | Relay module KMX5000 RK (32928) |
Item numbers according to the Detectomat fire detection product catalogue (as of 09/2026). Linear beam smoke detectors and flame detectors are tested as specified by the manufacturer.
Important
Before ordering
- Check the panel: Whether Loop3000 or CT 3000 detectors can be operated on your fire alarm control panel depends on the panel (e.g. dc3500), software version and programming. We check this using your detector list and programming file.
- Replacement interval: Smoke and multi-sensor detectors after 5 years at the latest, or after 8 years with automatic contamination compensation and testing in accordance with the manufacturer’s specifications – details under Deadlines & standards.
- Change of detector series: New bases, different detector types or a changed number of detectors may constitute a significant modification – see expert inspection and fire brigade.
- EN 54 tested (as of 19.10.2026): All Detectomat detectors listed as available are certified to EN 54-5 or EN 54-7 (multi-criteria detectors with CO additionally to EN 54-26/-29/-30). The detectors that are no longer available were approved under the EN 54 or VdS rules applicable when they were introduced; since 2008, CE marking to EN 54 has been mandatory for new detectors – which is why we only list currently certified types as replacements.
- Installation by a specialist company only: Replacement and repair of detectors in fire alarm systems required under building law are part of maintenance and are reserved for a specialist company certified to DIN 14675 – even if you only buy the detectors from us. Details under Legal situation.
- Order numbers are Detectomat item numbers (source: detectomat.com and dc3500 installer manual, last updated: 18.10.2026).
- Image credits and trademarks: Product images © detectomat. The images serve solely to identify the detectors. Brand and product names are the property of their respective owners. Further information in the Legal notice.
Not sure which detector is installed at your site?
Send us your detector list or a photo of the type plate. We will name the suitable replacement and tell you whether new bases are needed.